Detection Technology

Three common problems of loop resistance tester

time:2021/9/10   source:华天电力  reading:739 time

Three common problems and solutions for loop resistance testers


1. The loop resistance tester usually tests the current, and the Z value of the micro-ohm value is displayed as "1".


Cause: The voltage clamp is in the wrong position. The measured loop resistance value exceeds 2000. The voltage signal wire is disconnected or not opened.


Treatment: Process the voltage signal circuit, clamp and clamp the voltage clamp. When over-range: Use a multimeter to measure the voltage values of P1 and P2, and the resistance value = voltage value/current value.


Micro Ohmmeter.png


2. Press the "test switch" of the loop resistance tester, the ammeter has no current, and the Z height of the miniature ohmmeter displays "1".


Reason: The 100A current loop is not connected. The test switch is not closed.


Treatment: Check the test leads, reconnect, re-clamp, and then close the switch.


3. The loop resistance test is connected to a 220V AC power supply. The fan is not running, then press the "test switch". Ammeters and miniature western instruments are not shown.


Reason: 220V AC power supply is unavailable, and the fuse is not installed or blown.


Treatment: check and exclude. (100A instrument insurance is not less than 6A, then disconnect from the factory to solve the problem. (Do not connect DC or 380V AC power)