HuaTianLogo

Power detection technology / Power detection

Detection Technology

How to use dry test transformer

time:2021/8/1   source:华天电力  reading:651 time

(1) Before the test, the “” end of the shell of the dry-type test transformer and the ground “” of the power control box must be well grounded, otherwise it will endanger the safety of people and equipment.


(2) Before operation, you must be familiar with the electrical principle and wiring diagram of the high-voltage test transformer and the power control box. If checking the DC withstand voltage and leakage test, the high-voltage wah or micro-ampere meter can be screwed on the high-voltage end of the high-voltage test transformer first.



(3) After the preparation is completed and the wiring is checked, the main power switch can be turned on, and the red switch indicator light is also on at this time. If it does not light up, the regulator handle should be returned to the zero position in the counterclockwise direction, and the indicator light on the red stop button is on, otherwise the start button refuses to cooperate.


(4) Press the start button, and the green button indicator light is on. At this time, rotate the handle of the voltage regulator evenly and slowly at a speed of 1.5-2 kV per second clockwise, the high voltage gradually rises and pay close attention to the indication of the voltmeter and the test product Circumstances, until the required test high pressure is adjusted.


(5) To test the withstand voltage test time of the product, you can pull the timer for the required timing and then press the timing and alarm switch, that is, test the product withstand voltage within the specified time, and then give an alarm to notify if the tested product is hit The overcurrent relay will automatically trip. At this time, the reading of the voltmeter is the value of the breakdown voltage of the product.


(6) If you need to protect the product under test from breakdown, you can first connect the protective ball gap to the high-voltage side to adjust the discharge voltage of the protective ball to about 1.15 times the test voltage.


Copyright description: all articles, pictures, video and other materials on this site belong to wuhan huatian power automation co., LTD. For use, please contact us; Permission to reprint articles, pictures, video and other materials please quote "from: huatian power".

How to use insulation resistance tester  | 2021/8/1 | reading681time DC resistance tester to measure and discharge  | 2021/7/31 | reading594time return