Instructions for use of DC high voltage generator

time:2021/2/28   source:华天电力  reading:855 time

Instructions for use:


1. High-frequency output and voltage and current measuring cables are quickly connected to multi-core sockets: used to connect the chassis and the voltage doubling part. When connecting, just align the white dot on the cable plug with the white dot on the socket and turn it clockwise. When removing, just turn the cable plug counterclockwise. Note: When installing or removing the plug, please grip the metal ring of the plug and rotate it. It is strictly prohibited to hold the cable to rotate and pull the cable to rotate to avoid disconnection between the plug and the cable.


2. Power fuse holder: The fuse is 10A.


3. Power input socket: single-phase AC 220V±10%, 50Hz. Connect the power cord configured with the DC high voltage generator to the power input socket (the socket comes with a fuse 10A or a separate fuse holder).


DC Hipot Tester.png


4. Grounding terminal: After this grounding terminal is connected to the grounding terminal of the pressure doubler and the test product at one point, then it is connected to the grounding grid.


5. Overvoltage setting dial switch: used to set the overvoltage protection value. The overvoltage setting range is within 0.05-1.2 times the rated voltage, and the unit of the value displayed by the dial switch is kV.


6. Red button with light, high voltage switch on button, high voltage indicator light: when the green light is on, after pressing the red button, the red light is on and the green light is off, indicating that the high voltage circuit is connected. The voltage can be boosted at this time. This button is valid only when the voltage regulator potentiometer returns to zero. If you press the red button, the red light is on and the green light is still on, but when you release the button, the red light is off and the green light is on, indicating that the internal protection circuit is working. At this time, turn off the switch and check whether the overvoltage setting dial switch is less than 5% of the full scale and there is If there is no other fault, the DC high-voltage generator will be turned on again after the inspection is correct.