Transformer Resonant Test System

UHV-270kVA/108kVHigh Voltage Resonant Test System

Suitable for large capacity, high voltage capacitive test and preventive test

Reference standard: GB 50150-2016, DL/T 849.6-2016, DL/T 474.4-2018

Note: Regarding product purchase, technical maintenance and other services, welcome to send email:

Product Overview and Working Principle

The UHV-270kVA/108kV High Voltage Resonant Test System is designed for AC withstand voltage testing of high-voltage electrical equipment with capacitive characteristics. It can be configured for suitable test objects such as power cables, switchgear, and power transformers, provided that the required test voltage, capacitance, frequency, and test duration fall within the system's operating limits.

The resonant test system manufacturer uses the series resonance principle. By adjusting the output frequency of the variable frequency power supply, the inductive reactance of the high-voltage reactor can be matched with the capacitive reactance of the test object. When resonance is achieved, the system can generate the required test voltage with a comparatively low power supply requirement.

The main components include a variable frequency power supply, an excitation transformer, high-voltage reactors, and a capacitive voltage divider. The modular reactor configuration allows the system to be arranged for different test requirements, subject to the verified equipment ratings and the electrical characteristics of the test object.

Before selecting the equipment, users should confirm the required test voltage, test object capacitance, operating frequency, test duration, site power supply, and applicable testing standards.

Meet the test range

1. 10kV/300mm² cable 3km AC voltage test, capacitance ≤1.1265μF, test frequency 30-300Hz, test voltage 22kV, test time 5min.

2. 10kV switch and other substation equipment AC withstand voltage test, the test frequency is 30-300Hz, the test voltage does not exceed 42kV, the test time is 1min.

3. 35kV/300mm² cable 1km AC voltage test, capacitance ≤0.1945μF, test frequency 30-300Hz, test voltage 52kV, test time 60min.

4. AC voltage withstand test of 35kV/31500kVA main transformer, capacitance ≤0.02μF, test frequency 45-65Hz, test voltage 68kV, test time 1min.

5. 35kV switch and other electrical equipment AC voltage test, the test frequency is 30-300Hz, the test voltage does not exceed 95kV, the test time is 1min.

Main components of the device

Serial number Device name Specification and model Unit Quantity
1 Variable frequency power supply UHV-15kW Tower 1
2 Excitation transformer UHV-4kVA/1.5/3/6kV/0.4kV Tower 1
3 High voltage reactor UHV-67.5kVA/27kV Section 4
4 Capacitive voltage divider UHV-1500pF/110kV Set 1

Main technical parameters and functions

Rated capacity 270kVA
Rated voltage 27kV;54kV;108kV
Rated current 10A;5A;2.5A
Measurement accuracy System RMS level 1.5
Operating frequency 30-300Hz
Device output waveform Sinusoidal wave
Quality factor Device Q≥30(f=45Hz)
Waveform distortion rate Output voltage waveform distortion ≤1%
Input power supply Single-phase 220 or three-phase 380V voltage, frequency 50Hz
Working hours Allow continuous 60min under rated load; Overpressure 1.1 times 1 minute
Temperature rise Temperature rise ≤65K after continuous operation under rated load for 60 minutes
Protection function Overvoltage, overcurrent, zero start, system mismatch (flashover) and other protection functions
Ambient temperature -20℃-55℃
Relative humidity ≤90%RH
Altitude ≤3000m

Device capacity verification (device capacity is set at 135kVA, divided into four reactors, reactor single section is 33.75kVA/27kV/1.25A/100H)

Serial number Test Test Frequency Test Current
1 10kV/300mm² cable 3km AC voltage withstand test, capacitance ≤1.1265μF, test frequency 30-300Hz, test voltage 22kV, test time 5min. Use four reactors in parallel, L=100/4=25H f=1/2π√(LC)=1/(2×3.14×√(25×1.1265×10⁻⁶))=30Hz I=2πfCU=2π×30×1.1265×10⁻⁶×22×10³=4.67A
2 35kV/300mm² cable 1km AC voltage withstand test, capacitance ≤0.1945μF, test frequency 30-300Hz, test voltage 52kV, test time 60min. Use two reactors in series (mutual inductance coefficient 1.15) two groups in parallel, L=100×2×1.15/2=115H f=1/2π√(LC)=1/(2×3.14×√(115×0.1945×10⁶))=33.65Hz I=2πfCU=2π×33.65×0.1945×10⁻⁶×52×10³=2.14A
3 Ac voltage withstand test of 35kV/31500kVA main transformer, capacitance ≤0.02μF, test frequency 45-65Hz, test voltage 68kV, test time 1min. Use four reactors in series (mutual inductance coefficient 1.25), L=100×4×1.25=500H f=1/2π√(LC)=1/(2×3.14×√(500×0.02×10⁻⁶))=50.33Hz I=2πfCU=2π×50.33×0.02×10⁻⁶×68×10³=0.43A

Equipment combination method during testing

Test Object Combination Method
Reactor Selection
(33.75kVA/27kV Four Sections)
Excitation Transformer
Output Selection
Test Voltage
(kV)
10kV/300mm 2 Cable 3km Use four reactors in parallel 1.5kV ≤22kV
10kV switch and other substation equipment Use three reactors in series 3kV ≤42kV
35kV/300mm 2 Cable 1km Use two reactors in series and two groups in parallel 3kV ≤52kV
35kV/31500kVA main transformer Use four reactors in series 6kV ≤68kV
35kV switch and other electrical equipment Use four reactors in series 6kV ≤95kV

System Configuration Parameters

(One) Variable Frequency Power Supply UHV-15kW (1 unit)
Rated Output Capacity 15kW
Power Supply 220/380±10%V (Single/Three Phase), Power Frequency
Output Voltage 0-400V
Rated Input Current 37.5A
Rated Output Current 37.5A
Voltage Resolution 0.01kV
Voltage Measurement Accuracy 1.5%
Frequency Adjustment Range 30-300Hz
Frequency Adjustment Resolution ≤0.1Hz
Frequency Stability 0.1%
Operating Time Continuous 60min at Rated Capacity
Maximum Component Temperature at Continuous 60min Operation at Rated Capacity ≤65K
Noise Level ≤50dB
Dimensions (L×W×H mm) 460×340×420
Weight Approximately 15kg
(Two) Excitation Transformer UHV-15kVA/1.5/3/6kV/0.4kV (1 unit)
Rated Capacity 15kVA
Input Voltage 0-400V
Output Voltage 1.5/3/6kV
Structure Dry Type
Dimensions (L×W×H mm) 520×520×460
Weight Approximately 85kg
(Three) High Voltage Reactor UHV-67.5kVA/27kV (4 units)
Rated Capacity 67.5kVA
Rated Voltage 27kV
Rated Current 2.5A
Inductance 50H/unit
Quality Factor Q≥30(f=45Hz)
Structure Dry Type
Dimensions (Inner Diameter×Height mm) 382×435
Weight Approximately 90kg
(Four) Capacitive Voltage Divider UHV-1500pF/110kV (1 set)
Rated Voltage 110kV
High Voltage Capacitance 1500pF
Dielectric Loss tgσ≤0.5%
Voltage Division Ratio 1500:1
Measurement Accuracy Effective Value 1.5 Grade
Dimensions (Inner Diameter×Height mm) 140×1000
Weight Approximately 8kg

Delivery List

No. Equipment Name Model and Specifications Unit Quantity
1 Variable Frequency Power Supply UHV-15kW Unit 1
2 Excitation Transformer UHV-15kVA/1.5/3/6kV/0.4kV Unit 1
3 High Voltage Reactor UHV-67.5kVA/27kV Section 4
4 Capacitive Voltage Divider UHV-1500pF/110kV Set 1
5 Internal Connection Cables
Set 1
6 Factory Inspection Report
Copy 1
7 User Manual
Copy 1
8 Product Certificate
Copy 1
9 Packing List
Copy 1

Reference Test Standards

DL/T 596-1996 "Preventive Test Code for Electric Power Equipment"
GB50150-2016 "Standard for Handover Testing of Electrical Equipment in Electrical Installation Engineering"
GB10229-88 "Reactors"
GB1094 "Power Transformers"
GB1094.1-GB1094.6-96 "Degrees of Protection Provided by Enclosures"
GB2900 "Electrotechnical Terminology"
GB/T16927.1~2-1997 "High Voltage Test Techniques"
DL/T474.4-2006 "Guide for Insulation Test Implementation on Site - AC Withstand Voltage Test"
DL/T1015 "Guide for the Use of Voltage Measurement Systems for On-site DC and AC Withstand Voltage Tests"
GB/T311.1-1997 "Insulation Coordination and Insulation of High Voltage Power Transmission and Transformation Equipment"
GB191-2000 "Pictorial Markings for Packaging and Storage"
JB/T9641-1999 "Test Transformers"
IEC358(1990) "Coupling Capacitors and Capacitor Dividers"
GB4793-1984 "Safety Requirements for Electronic Measuring Instruments"
GB/T3859.2-1993 "Application Guide for Semiconductor Converters"
GB/T2423.8-1995 "Basic Environmental Testing Procedures for Electrical and Electronic Products"
DL/T849.6-2004 "General Technical Specifications for Special Test Instruments for Power Equipment Part 6: High Voltage Frequency Tuning Test Devices"

Comparison series resonant test systems

Product Model Primary Application Rating(Capacity/Voltage) Key Features
UHV-75kVA/75kV AC Resonant Test System Smaller capacity cables & switchgear 75kVA/75kV Entry-level system for shorter cables and lower voltage tests; cost-effective with a simpler configuration (3 reactors).
UHV-135kVA/108kV Resonant Test Set for Cable Medium-voltage cables & substation equipment 135kVA/108kV Optimized for 10kV and 35kV cables; flexible configuration (4 reactors); lightweight and portable for field testing.
UHV-270kVA/108kV High Voltage Resonant Test System Longer or higher voltage cables 270kVA/108kV Higher capacity for testing longer cable runs or cables with higher voltage ratings; overlaps with the 135kVA system's application but offers greater capability.
UHV-405kVA/270kV Cable Resonant Test Set High/Ultra-high voltage cables 405kVA/270kV Specifically designed for high-voltage cables (e.g., 110kV, 220kV) with significantly increased voltage and capacity.
UHV-540kVA/270kV High Voltage Test Set for 500kV GIS 500kV GIS & other large capacitive loads 540kVA/270kV Highest capacity and voltage rating; designed for 500kV GIS substations and other EHV equipment, typically used for commissioning tests.

Product Comparison

Comparing dimensions Series resonance Power frequency transformer Very low frequency (0.1Hz)
Core Advantages Lightweight power supply, no impact during breakdown, good equivalence Absolute frequency, pure waveform Extremely lightweight and safe for low voltage operation
Fatal weakness High equipment cost and high requirements for variable frequency power supply Extremely bulky, breakdown can burn the test sample Long testing time and not recognized by all standards
Most suitable 220kV and above cables, GIS switches Transformers and insulators below 10kV Quick troubleshooting of medium and low voltage cables (length ≤ 5km)
Note:

1.The appearance of the product shall be subject to the actual product,Technical parameters with model if there are any changes,without notice.In case of misappropriation or copying, legal liability will be investigated.

2. For more information about Wuhan UHV, please enter product center . Service email:info@hvtest.cc

Main Functions and Features

The main functions and technical characteristics of the frequency-modulation resonance device of our company:

1. the resonant test system has overvoltage, overcurrent, zero start, system mismatch (flashover) and other protection functions, overvoltage and overcurrent protection value can be adjusted according to user needs, flashover protection action when the test product flashover and can record the flashover voltage value for test analysis.

2. the whole device single weight is very light, easy to use on site.

3. the resonant test system has three working modes: automatic mode, manual mode, automatic tuning manual boost mode; Convenient for users to flexibly choose according to the field situation, improve the test speed.

4. can store and remote print data, stored data number is a number, easy for users to identify and find.

5. when the resonant test system automatically sweeps the frequency starting point can be arbitrarily set within the specified range, the scanning direction can be selected up and down, and the LCD large screen displays the scanning curve, which is convenient for users to intuitively understand whether to find the resonance point.

6. the use of DSP platform technology, according to user needs to increase or decrease the function and upgrade, human-machine exchange interface is more humane.

7. the required power capacity is greatly reduced. Series resonant power supply is the use of resonant reactor and the test product capacitor resonance to produce high voltage and high current, in the whole system, the power supply only needs to provide the active power consumption of the system, so the power required for the test is only 1/Q of the test capacity.

8. the weight and volume of the equipment are greatly reduced. In the series resonant device, the bulky high-power voltage regulator and the ordinary high-power power frequency test transformer are omitted, and the resonant excitation power supply only needs 1/Q of the test capacity, which greatly reduces the weight and volume of the system, generally 1/10-1/30 of the ordinary test device.

9. effectively improve the output voltage waveform. The resonant power supply is a resonant filter circuit, which can improve the waveform distortion of the output voltage, obtain a good sinusoidal waveform, and effectively prevent the harmonic peak to the test product.

10. prevent large short circuit current burn fault point. In the series resonance state, when the insulation weakness of the test product is broken down, the circuit is immediately detuned, the loop current rapidly drops to 1/Q of the normal test current, and when the parallel resonance or test transformer is used for voltage resistance test, the breakdown current immediately rises dozens of times, compared with the two, the short circuit current and the breakdown current are hundreds of times different. The series resonance can effectively find the insulation weakness, and there is no large short-circuit current burn fault point worry.

11. No recovery overvoltage will occur. When the test product breaks down, due to the loss of resonance conditions, the high voltage also immediately disappears, the arc is immediately extinguished, and the re-establishment process of the recovery voltage is very long, it is easy to disconnect the power supply before reaching the flashover voltage again, the recovery process of this voltage is a kind of intermittent oscillation process of energy accumulation, its process is long, and there will be no recovery overvoltage.

How to Select the Right Series Resonant Test System

Selecting a high-voltage series resonant test system requires more than checking the rated output voltage. The electrical characteristics of the test object and the required test conditions must be considered together.

1. Rated Test Voltage: Confirm the required AC withstand voltage according to the applicable standard and the test object specifications.

2. Test Object Capacitance: Determine or calculate the total capacitance of the test object and associated connections. This value directly affects the resonant frequency and the current required during testing.

3. Test Frequency and Duration: Check whether the required test frequency and test duration fall within the system's specified operating limits.

4. Reactor Configuration: The number and arrangement of the reactors should be selected according to the required inductance, test voltage, current, and total capacitance.

5. Site Power Supply: Confirm the available input voltage, phase configuration, power capacity, and site operating conditions.

6. Environmental Conditions: Consider ambient temperature, relative humidity, altitude, transportation requirements, and available installation space.

Applications of the High Voltage Resonant Test System

Testing Procedure and Site Preparation

FAQ

Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device

Product Certificate

Enterprise products in strict accordance with international and national standards and rules of industry production, through the national, provincial and municipal electric power research institute and electric power authorities detection, measuring center, fully passed the ISO9001 international quality management system certification, the licence for manufacturing measuring instruments of the People's Republic of China, GB/T19001-2016 quality management system requirements, GB/T24001-2016 environmental management system requirements, GB/T45001-2020 occupational health and safety management system requirements.