Series resonance device

UHV-270kVA/10kV Series Resonance Solution

Suitable for large capacity, high voltage capacitive test and preventive test

Reference standard: GB 50150-2016, DL/T 849.6-2016, DL/T 474.4-2018

Note: Regarding product purchase, technical maintenance and other services, welcome to send email:

Meet the test range

1, 10kV/300mm² cable 3km AC voltage test, capacitance ≤1.1265μF, test frequency 30-300Hz, test voltage 22kV, test time 5min.

2, 10kV switch and other substation equipment AC withstand voltage test, the test frequency is 30-300Hz, the test voltage does not exceed 42kV, the test time is 1min.

3, 35kV/300mm² cable 1km AC voltage test, capacitance ≤0.1945μF, test frequency 30-300Hz, test voltage 52kV, test time 60min.

4, AC voltage withstand test of 35kV/31500kVA main transformer, capacitance ≤0.02μF, test frequency 45-65Hz, test voltage 68kV, test time 1min.

5, 35kV switch and other electrical equipment AC voltage test, the test frequency is 30-300Hz, the test voltage does not exceed 95kV, the test time is 1min.

Main components of the device

Serial number Device name Specification and model Unit Quantity
1 Variable frequency power supply UHV-15kW Tower 1
2 Excitation transformer UHV-4kVA/1.5/3/6kV/0.4kV Tower 1
3 High voltage reactor UHV-67.5kVA/27kV Section 4
4 Capacitive voltage divider UHV-1500pF/110kV Set 1

Main Functions and Features

UHV-135kVA/108kV series resonance scheme, using the way to adjust the frequency of the power supply, so that the reactor and the tested capacitor achieve resonance, so as to obtain high voltage and high current on the test product, because of its small power supply required, light weight and small volume of the equipment, has been widely praised and applied at home and abroad, is the current high voltage test of the new method and trend.

The main functions and technical characteristics of the frequency-modulation resonance device of our company:

1, the device has overvoltage, overcurrent, zero start, system mismatch (flashover) and other protection functions, overvoltage and overcurrent protection value can be adjusted according to user needs, flashover protection action when the test product flashover and can record the flashover voltage value for test analysis.

2, the whole device single weight is very light, easy to use on site.

3, the device has three working modes: automatic mode, manual mode, automatic tuning manual boost mode; Convenient for users to flexibly choose according to the field situation, improve the test speed.

4, can store and remote print data, stored data number is a number, easy for users to identify and find.

5, when the device automatically sweeps the frequency starting point can be arbitrarily set within the specified range, the scanning direction can be selected up and down, and the LCD large screen displays the scanning curve, which is convenient for users to intuitively understand whether to find the resonance point.

6, the use of DSP platform technology, according to user needs to increase or decrease the function and upgrade, human-machine exchange interface is more humane.

7, the required power capacity is greatly reduced. Series resonant power supply is the use of resonant reactor and the test product capacitor resonance to produce high voltage and high current, in the whole system, the power supply only needs to provide the active power consumption of the system, so the power required for the test is only 1/Q of the test capacity.

8, the weight and volume of the equipment are greatly reduced. In the series resonant device, the bulky high-power voltage regulator and the ordinary high-power power frequency test transformer are omitted, and the resonant excitation power supply only needs 1/Q of the test capacity, which greatly reduces the weight and volume of the system, generally 1/10-1/30 of the ordinary test device.

9, effectively improve the output voltage waveform. The resonant power supply is a resonant filter circuit, which can improve the waveform distortion of the output voltage, obtain a good sinusoidal waveform, and effectively prevent the harmonic peak to the test product.

10, prevent large short circuit current burn fault point. In the series resonance state, when the insulation weakness of the test product is broken down, the circuit is immediately detuned, the loop current rapidly drops to 1/Q of the normal test current, and when the parallel resonance or test transformer is used for voltage resistance test, the breakdown current immediately rises dozens of times, compared with the two, the short circuit current and the breakdown current are hundreds of times different. The series resonance can effectively find the insulation weakness, and there is no large short-circuit current burn fault point worry.

11, No recovery overvoltage will occur. When the test product breaks down, due to the loss of resonance conditions, the high voltage also immediately disappears, the arc is immediately extinguished, and the re-establishment process of the recovery voltage is very long, it is easy to disconnect the power supply before reaching the flashover voltage again, the recovery process of this voltage is a kind of intermittent oscillation process of energy accumulation, its process is long, and there will be no recovery overvoltage.

Main technical parameters and functions

Rated capacity 270kVA
Rated voltage 27kV;54kV;108kV
Rated current 10A;5A;2.5A
Measurement accuracy System RMS level 1.5
Operating frequency 30-300Hz
Device output waveform Sinusoidal wave
Quality factor Device Q≥30(f=45Hz)
Waveform distortion rate Output voltage waveform distortion ≤1%
Input power supply Single-phase 220 or three-phase 380V voltage, frequency 50Hz
Working hours Allow continuous 60min under rated load; Overpressure 1.1 times 1 minute
Temperature rise Temperature rise ≤65K after continuous operation under rated load for 60 minutes
Protection function Overvoltage, overcurrent, zero start, system mismatch (flashover) and other protection functions
Ambient temperature -20℃-55℃
Relative humidity ≤90%RH
Altitude ≤3000m

Device capacity verification (device capacity is set at 135kVA, divided into four reactors, reactor single section is 33.75kVA/27kV/1.25A/100H)

Serial number Test Test Frequency Test Current
1 10kV/300mm² cable 3km AC voltage withstand test, capacitance ≤1.1265μF, test frequency 30-300Hz, test voltage 22kV, test time 5min. Use four reactors in parallel, L=100/4=25H f=1/2π√(LC)=1/(2×3.14×√(25×1.1265×10⁻⁶))=30Hz I=2πfCU=2π×30×1.1265×10⁻⁶×22×10³=4.67A
2 35kV/300mm² cable 1km AC voltage withstand test, capacitance ≤0.1945μF, test frequency 30-300Hz, test voltage 52kV, test time 60min. Use two reactors in series (mutual inductance coefficient 1.15) two groups in parallel, L=100×2×1.15/2=115H f=1/2π√(LC)=1/(2×3.14×√(115×0.1945×10⁶))=33.65Hz I=2πfCU=2π×33.65×0.1945×10⁻⁶×52×10³=2.14A
3 Ac voltage withstand test of 35kV/31500kVA main transformer, capacitance ≤0.02μF, test frequency 45-65Hz, test voltage 68kV, test time 1min. Use four reactors in series (mutual inductance coefficient 1.25), L=100×4×1.25=500H f=1/2π√(LC)=1/(2×3.14×√(500×0.02×10⁻⁶))=50.33Hz I=2πfCU=2π×50.33×0.02×10⁻⁶×68×10³=0.43A

Equipment combination method during testing

Test Object Combination Method
Reactor Selection
(33.75kVA/27kV Four Sections)
Excitation Transformer
Output Selection
Test Voltage
(kV)
10kV/300mm 2 Cable 3km Use four reactors in parallel 1.5kV ≤22kV
10kV switch and other substation equipment Use three reactors in series 3kV ≤42kV
35kV/300mm 2 Cable 1km Use two reactors in series and two groups in parallel 3kV ≤52kV
35kV/31500kVA main transformer Use four reactors in series 6kV ≤68kV
35kV switch and other electrical equipment Use four reactors in series 6kV ≤95kV

System Configuration Parameters

(一) Variable Frequency Power Supply UHV-15kW (1 unit)
Rated Output Capacity 15kW
Power Supply 220/380±10%V (Single/Three Phase), Power Frequency
Output Voltage 0-400V
Rated Input Current 37.5A
Rated Output Current 37.5A
Voltage Resolution 0.01kV
Voltage Measurement Accuracy 1.5%
Frequency Adjustment Range 30-300Hz
Frequency Adjustment Resolution ≤0.1Hz
Frequency Stability 0.1%
Operating Time Continuous 60min at Rated Capacity
Maximum Component Temperature at Continuous 60min Operation at Rated Capacity ≤65K
Noise Level ≤50dB
Dimensions (L×W×H mm) 460×340×420
Weight Approximately 15kg
(二) Excitation Transformer UHV-15kVA/1.5/3/6kV/0.4kV (1 unit)
Rated Capacity 15kVA
Input Voltage 0-400V
Output Voltage 1.5/3/6kV
Structure Dry Type
Dimensions (L×W×H mm) 520×520×460
Weight Approximately 85kg
(三) High Voltage Reactor UHV-67.5kVA/27kV (4 units)
Rated Capacity 67.5kVA
Rated Voltage 27kV
Rated Current 2.5A
Inductance 50H/unit
Quality Factor Q≥30(f=45Hz)
Structure Dry Type
Dimensions (Inner Diameter×Height mm) 382×435
Weight Approximately 90kg
(四) Capacitive Voltage Divider UHV-1500pF/110kV (1 set)
Rated Voltage 110kV
High Voltage Capacitance 1500pF
Dielectric Loss tgσ≤0.5%
Voltage Division Ratio 1500:1
Measurement Accuracy Effective Value 1.5 Grade
Dimensions (Inner Diameter×Height mm) 140×1000
Weight Approximately 8kg

Delivery List

No. Equipment Name Model and Specifications Unit Quantity
1 Variable Frequency Power Supply UHV-15kW Unit 1
2 Excitation Transformer UHV-15kVA/1.5/3/6kV/0.4kV Unit 1
3 High Voltage Reactor UHV-67.5kVA/27kV Section 4
4 Capacitive Voltage Divider UHV-1500pF/110kV Set 1
5 Internal Connection Cables
Set 1
6 Factory Inspection Report
Copy 1
7 User Manual
Copy 1
8 Product Certificate
Copy 1
9 Packing List
Copy 1

Reference Test Standards

DL/T 596-1996 "Preventive Test Code for Electric Power Equipment"
GB50150-2016 "Standard for Handover Testing of Electrical Equipment in Electrical Installation Engineering"
GB10229-88 "Reactors"
GB1094 "Power Transformers"
GB1094.1-GB1094.6-96 "Degrees of Protection Provided by Enclosures"
GB2900 "Electrotechnical Terminology"
GB/T16927.1~2-1997 "High Voltage Test Techniques"
DL/T474.4-2006 "Guide for Insulation Test Implementation on Site - AC Withstand Voltage Test"
DL/T1015 "Guide for the Use of Voltage Measurement Systems for On-site DC and AC Withstand Voltage Tests"
GB/T311.1-1997 "Insulation Coordination and Insulation of High Voltage Power Transmission and Transformation Equipment"
GB191-2000 "Pictorial Markings for Packaging and Storage"
JB/T9641-1999 "Test Transformers"
IEC358(1990) "Coupling Capacitors and Capacitor Dividers"
GB4793-1984 "Safety Requirements for Electronic Measuring Instruments"
GB/T3859.2-1993 "Application Guide for Semiconductor Converters"
GB/T2423.8-1995 "Basic Environmental Testing Procedures for Electrical and Electronic Products"
DL/T849.6-2004 "General Technical Specifications for Special Test Instruments for Power Equipment Part 6: High Voltage Frequency Tuning Test Devices"
Note:

1.The appearance of the product shall be subject to the actual product,Technical parameters with model if there are any changes,without notice.In case of misappropriation or copying, legal liability will be investigated.

2. For more information about Wuhan UHV, please enter product center . Service email:info@hvtest.cc

Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device Series resonance device

Product Video

Product Certificate

Enterprise products in strict accordance with international and national standards and rules of industry production, through the national, provincial and municipal electric power research institute and electric power authorities detection, measuring center, fully passed the ISO9001 international quality management system certification, the licence for manufacturing measuring instruments of the People's Republic of China, GB/T19001-2016 quality management system requirements, GB/T24001-2016 environmental management system requirements, GB/T45001-2020 occupational health and safety management system requirements.